Application/type: Room sensor
Intended use: Measurement value acquisition
Measured variables: Temperature, relative humidity, absolute humidity, enthalpy, dew point
Interface: Active, 0..5 V, 0..10 V
Configuration: USEapp, uConfig, jumper
Voltage output: 2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
Temperature application range (°C): -40..+120
Output signal temperature: scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, adjustable at the transmitter
Temperature application range housing (°C): electronics -35..+70
Humidity application range: max. 85% rH not permanently condensing
Accuracy temperature: ±0.3 K (typ. at 21 °C), in standard measuring range, potentiometer for offset setting, offset setting via App or uConfig
Measuring range humidity: 0..100% rH without condensation, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, adjustable at the transmitter
Accuracy humidity: ±2% between 10..90% rH (typ. at 21 °C), potentiometer for offset adjustment
Power supply: 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV
Power consumption: typ. 0.4 W (24 V =), 0.8 VA (24 V ~)
Material in contact with medium: sensor head, Ø=13 mm, sensor tip Ø=7 mm, stainless steel V2A (1.4305)
Fitting length (mm): 35
Housing: USE-M, impact and break-proof housing with hinged cover, PC
Colour: pure white
Protection class:enclosure IP65, according to DIN EN 60529
Connection: removable cable entry Flextherm M20 for cables with Ø=4.5..9 mm, removable plug-in terminal, max. 2.5 mm²
Connection cable: PVC, 0.14 mm², grey
Length of connection cable (m): 15
Installation: plastering or installation in cavity walls
Scope of delivery: incl. mounting base. Mounting base USE-M enclosure pure white, incl. Mounting set (screws and accessories)
Unit length (mm): 85
Unit width (mm): 84
Unit height (mm): 85
Option housing: LCD 29x35 mm, RGB backlighting